NFPA 96 in Quebec Condominiums: Restaurant Ventilation

By Muriel Druart, Client services director

When a restaurant moves into the ground floor of a divided co-ownership, ventilation becomes a priority. Commercial hoods, ducts and rooftop fans move greasy vapours and smoke which, if poorly managed, create odours, noise and, above all, a fire risk. The technical standard commonly referenced in North America for these installations is NFPA 96.

In Quebec, practical application is based on the Safety Code (Chapter VIII – Building, NBC) and the Construction Code, to which local authorities and the RBQ refer. In a mixed-use condominium (residential + commercial), the board of directors must therefore understand how NFPA 96 fits into this framework, how to allocate responsibilities between private portions and common portions, and what maintenance records to require from the restaurateur. The points below are current as of 2026-09-08.

Before getting started, you will benefit from organizing the information in the maintenance logbook (EUC) and setting out clear requirements in the building’s by-laws, in keeping with the declaration of co-ownership.

Understanding NFPA 96 in a Quebec Condominium

  • What NFPA 96 is. It is a North American technical standard covering ventilation and the control of greasy vapours produced by commercial cooking. It addresses Type I hoods, ducts, fans, fire protection and maintenance.
  • Its status in Quebec. The main legal references remain the Safety Code (Chapter VIII – Building, incorporating the NBC with modifications) and the Construction Code of Québec. Several municipalities and fire departments refer to NFPA 96 when assessing commercial kitchen compliance. Always verify the requirements of your authority having jurisdiction (local fire department and RBQ).
  • Why it is critical in a condominium. Commercial kitchen ducts often pass through common portions (ceilings, shafts and the roof). A failure can spread fire, odours and grease to residential units. This raises safety, civil liability (see the C.C.Q.) and insurance issues.

Useful official resources:

  • Safety Code, Chapter VIII – Building (modified NBC): LégisQuébec.
  • Construction Code, Chapter I – Building: LégisQuébec.
  • Fire Safety Act: LégisQuébec.
  • RBQ (general) for system compliance and maintenance.

Key Technical Requirements for Commercial Kitchens

Without reproducing the standard, here are the elements typically reviewed when a restaurant operates on the ground floor of a condominium:

  • Type I hood with approved baffle filters, readily accessible for cleaning and visual inspection.
  • Continuous metal ducts, with slopes allowing grease to flow into collection trays, sealed joints and access panels at suitable intervals for mechanical cleaning.
  • Enclosure and fire separations. Ducts passing through common areas and fire separations must comply with the fire-resistance rating prescribed by the Construction Code and the Safety Code. Penetration sealing (firestopping) must be maintained.
  • Rooftop exhaust fan with a grease collector, deflector and protection against accumulation on the membrane. It must be located an adequate distance from residential fresh-air intakes to prevent odours from recirculating.
  • Make-up air to balance pressure and reduce odour infiltration into corridors and private portions.
  • Emergency shutoff, control devices and interlocking with the automatic extinguishing system (wet chemical type) for the cooking line.
  • Access signage and clearances for safe maintenance, including on the roof.
  • Noise and vibration management (supports and silencers) to respect the co-owners’ peace and quiet.

In a mixed-use building, the board should confirm that the design was sealed by a professional and that a qualified contractor installed the entire system in accordance with the plans and applicable requirements. Document these elements in the EUC, including serial numbers, access-panel locations and as-built diagrams.

Maintenance and Cleaning: Frequencies, Records and Audits

Regular maintenance is at the heart of fire and odour risk management for a restaurant in a condominium. In practice:

  • Frequencies. Depending on cooking intensity (grilling, frying and volume), the frequency of internal hood and duct cleaning generally ranges from monthly to semi-annually; many high-volume establishments schedule quarterly cleaning. Confirm with your fire department and the applicable requirements.
  • Who performs it. Hire a company specializing in commercial hood and duct cleaning that can install certification plates and provide illustrated reports (before-and-after photos).
  • Required records. Keep cleaning certificates, work orders, dated photos, labels affixed to the hood and maintenance logs. Reference them in the maintenance logbook/EUC.
  • Visual inspection. Between cleanings, a simple visual check by the operator (accumulation on filters and trays) can trigger early intervention.
  • Automatic extinguishing. Test and maintain the kitchen extinguishing system according to the manufacturer’s intervals and the NBC requirements. Keep the certificates with the building’s other fire-safety records.
  • Roof. Monitor grease accumulation around the fan. Grease damages membranes and can lead to a loss. Plan regular maintenance and effective retention trays.

Good governance practices for the board:

  • Add clauses to the building’s by-laws covering minimum maintenance, documentary proof and access to commercial private portions for inspection (in accordance with the declaration of co-ownership and applicable laws).
  • Add due-date reminders to the syndicate’s annual maintenance calendar and record the condition of the systems in the AGM minutes to ensure follow-up.
  • When necessary, plan an independent audit (by a building mechanical professional) when odour complaints persist or a major modification is being considered.

For an overview of coordinated condominium operations and maintenance services, see our Services – Operations Management.

Who Does What? The Syndicate, Board, Restaurateur and Contractors

  • Syndicate (common portions). The syndicate is responsible for preserving the building and ensuring the safety of the common portions. When a hood duct passes through a common shaft or exits through the roof, the fire separation integrity, sealing and maintenance of the building envelope are generally the syndicate’s responsibility. If the common portions are damaged because of inadequate maintenance of an extraction system serving a commercial private portion, liability may arise (see section 1077 of the C.C.Q.).
  • Commercial co-owner / restaurateur (private portion). The restaurateur operates the activity that creates the risks. They must have their equipment installed, used and maintained in accordance with applicable requirements and allow reasonable access for inspections and work necessary to maintain safety.
  • Board of directors. The board ensures that the declaration of co-ownership and the building’s by-laws are applied, adopts rules of use (ventilation hours and noise levels) and requires maintenance records. The board may impose corrective measures and, when necessary, recover additional costs caused by the commercial activity in accordance with the declaration of co-ownership and applicable laws.
  • Contractors and professionals. The board should require proof of competence (licences and insurance) from contractors who install or clean hoods and ducts, as well as professional validation of the work when necessary.

Budgeting and insurance:

  • Include roof repairs, fan accessories and firestopping in the multi-year contingency fund plan if these elements are common. Major replacements (for example, a dedicated common rooftop fan) should appear in your expenditure plan.
  • Contact the syndicate’s insurer and the restaurateur’s insurer. Several insurers request recent cleaning and maintenance certificates; otherwise, coverage restrictions may apply.

Recommended process for a mixed-use condominium (summary):

  1. Before opening: validate the compliance of the plans (ventilation, fire separations and rooftop outlet) and their integration with common systems; obtain the required approvals.
  2. During operations: require maintenance contracts and periodic certificates, record the evidence in the EUC, monitor nuisances (odours and noise) and make adjustments as needed.
  3. At the AGM: present a status report, completed work and planned budgets; document decisions in the minutes.

For additional resources, also consult our blog.

FAQ — NFPA 96 in a Condominium

Q1. Is a café without a deep fryer covered by NFPA 96?
It depends on the appliances and type of cooking. As soon as significant greasy vapours or cooking smoke are produced, a Type I hood system and exhaust duct may be required by the authority having jurisdiction. Confirm with your local fire department and refer to the NBC framework in Quebec.

Q2. Who pays for work on a duct that passes through the common portions?
Generally, repairs to common elements are the syndicate’s responsibility, with the possibility of charging certain costs to the commercial co-owner if the cause is related to their use (according to the declaration of co-ownership, the building’s by-laws and the law). Obtain legal advice to allocate costs fairly and document the decision in the minutes.

Q3. What records may the insurer request?
Hood and duct cleaning certificates, kitchen extinguishing-system maintenance reports, dated photos, invoices and contracts. Keep these documents in the EUC; they will be useful in the event of a loss or claim.


Official references:

  • LégisQuébec – Safety Code, Chapter VIII – Building (modified NBC)
  • LégisQuébec – Construction Code, Chapter I – Building
  • LégisQuébec – Fire Safety Act
  • LégisQuébec – Civil Code of Québec (C.C.Q.)
  • RBQ – Régie du bâtiment du Québec
  • RGCQ – Regroupement des gestionnaires et copropriétaires du Québec

This article provides general information and does not constitute legal advice. For your situation, consult a lawyer or notary.

Do you manage a condominium in Quebec? Discover our plans or contact us to assess your needs.

Managing your condo building with multiRent

  • Condo management services
  • Condo maintenance logbook
  • Condo management pricing

Areas served: South Shore · Montreal · Laval · Longueuil · Brossard · Boucherville · Saint-Constant · Saint-Amable · Saint-Jérôme

Share

Related posts

04/11/2026

Concierge or Outsourced Maintenance in a Co-ownership


Read more
21/10/2026

Mice and Rats in a Co-ownership: Who Pays?


Read more
06/10/2026

Condo Renovation Security Deposits in Quebec


Read more

Comments are closed.

multiRent — Gestion de copropriétés

Services

Administrative management

Financial management

Operations management

Portal

About Us

The multiRent team

Contact us

Notaries

LinkedIn

RGCQCorporate member of the RGCQ

Resources

RGCQ

CORPIQ

Portal
    Manage Consent

    To give you the best possible experience, we use technologies such as cookies to store and/or access information about your device. Consenting to these technologies lets us process data such as browsing behaviour or unique identifiers on this site. Declining or withdrawing your consent may affect certain features.

    Functional Always active
    Technical storage or access is strictly necessary for the legitimate purpose of enabling the use of a specific service explicitly requested by the subscriber or user, or for the sole purpose of carrying out the transmission of a communication over an electronic communications network.
    Preferences
    The technical storage or access is necessary for the legitimate purpose of storing preferences that are not requested by the subscriber or user.
    Statistics
    The technical storage or access that is used exclusively for statistical purposes. Technical storage or access used exclusively for anonymous statistical purposes. Without a subpoena, voluntary compliance on the part of your internet service provider, or additional records from a third party, information stored or retrieved for this purpose alone cannot usually be used to identify you.
    Marketing
    Technical storage or access is required to create user profiles in order to send advertising, or to track the user across a website or several websites for similar marketing purposes.
    • Manage options
    • Manage services
    • Manage {vendor_count} vendors
    • Read more about these purposes
    Manage preferences
    • {title}
    • {title}
    • {title}