Condo Fire Pumps in Quebec: NFPA 20, Testing

By Muriel Druart, Client services director

A well-maintained fire pump protects lives and reduces the extent of damage in a disaster. In a divided co-ownership, it supplies sprinklers and dry or wet standpipes at the required pressure. Your board of directors (the board) must understand its obligations in order to schedule testing, document maintenance and budget appropriately.

This practical guide summarizes the Quebec framework (NFPA 20 and NFPA 25), testing frequencies, essential tasks and expected documentation. You will also find practical advice adapted to syndicates and condo managers in Montreal and on the South Shore.

Standards and obligations in Quebec

In Quebec, the installation of a fire pump generally refers to NFPA 20, while the inspection, testing and maintenance of water-based fire-extinguishing systems refer to NFPA 25. These references are incorporated into the Quebec Safety Code, Building chapter, and supplemented by the regulations of the Régie du bâtiment du Québec (RBQ). (Current as of 2026-09-04.)

  • The syndicate is required to ensure the preservation of the building and the safety of individuals, which includes fire protection systems, under the Civil Code of Québec (see the general principles of the C.C.Q.).
  • The Quebec Safety Code requires periodic maintenance and record-keeping for fire protection devices.
  • The RBQ requires specialized work to be carried out by contractors holding the appropriate licence subclass for fire protection.

For more information:

  • Safety Code, Building chapter (LégisQuébec)
  • Civil Code of Québec (general principles)
  • Fire safety – RBQ
  • Check a contractor – RBQ

Key components of a fire pump assembly

In a typical condo pump room, you will find:

  • Main fire pump, coupled to an electric or diesel motor.
  • Jockey pump (pressure-maintenance pump), which maintains system pressure and prevents the main pump from starting frequently.
  • Fire pump controller, with automatic start devices activated by a pressure drop and manual start capability.
  • Test and discharge header, OS&Y isolation valve(s), check valves and suction/discharge pressure gauges.
  • Alarm devices, pressure switches, relief valve(s), leak detection, wiring and emergency power supply, depending on the building’s design.

These pieces of equipment are common portions. Their access, testing and maintenance must be recorded in the maintenance logbook / EUC and managed by the syndicate.

Testing and maintenance: minimum frequencies (current as of 2026-09-04)

The frequencies below reflect the intent of NFPA 25 and recognized practices. Always verify the edition applicable under the Quebec Safety Code and the instructions provided by your specialized contractor.

  • Periodic visual inspection: check for leaks, unusual noises, gauges, valve positions, seals and labels. We recommend a weekly round by the caretaker or manager.
  • Automatic start test: start the pump by creating a pressure drop through the controller and confirm the expected pressure recovery. The frequency varies according to the power supply and type of drive (for example, more frequently for diesel). Refer to NFPA 25 for the minimum operating duration.
  • Scheduled preventive maintenance: lubrication, bearing and alignment checks, battery, alarm and pressure-switch testing, air purging and vibration monitoring.
  • Annual flow test: measure the operating point, rated flow and churn pressure point using the test header and an appropriate measuring device. This test must be entrusted to a licensed fire protection contractor.

Typical procedure and safety

Before any test, post safety instructions and keep an active means of communication available. Here is a typical procedure for a start test and a flow test:

  1. Secure the area: restrict access to the pump room, require PPE and keep an emergency plan readily available.
  2. Check valve positions: suction and discharge valves open, check valves operational and no obstructions.
  3. Read and record the initial suction/discharge pressures and alarm status.
  4. Create a controlled pressure drop to trigger the automatic start.
  5. Monitor the pressure increase, vibration behaviour and noises; record current intensity or temperature, depending on the configuration.
  6. For the flow test, gradually open the test header outlets according to the contractor’s procedure to reach the required points.
  7. Record the measured values and durations; verify that fault alarms are silent and indicator lights are green.
  8. Return the system to normal, put all valves back in position, remove the testing devices and return the controller to automatic mode.
  9. Clean the room and record the results immediately in the log.

Common errors to avoid include leaving an isolation valve closed after testing, forgetting to return the controller to automatic mode, overlooking unusual noise or vibration, and ignoring a minor leak. Any deviation observed must lead to an inspection by a qualified contractor.

Who does what?

  • Caretaker/manager: visual rounds, checking labels and seals, recording pressures and alarm status, and reporting to the board.
  • Licensed contractor (fire protection): annual flow tests, specialized preventive maintenance, calibration and repairs.
  • Board/syndicate: approval of the maintenance plan, follow-up on non-compliances, budgeting and publishing a summary for co-owners at the AGM.

To structure these tasks, see our Operations Management Services: multiRent services – operations management.

Records, RBQ compliance and the syndicate’s budget

Keeping records is essential. Record the following in the maintenance logbook / EUC: the date, type of test, measurements, anomalies, corrective action and the name of the person responsible. Keep signed reports, technical data sheets and contractor certificates.

  • Testing and maintenance register: keep it on site and in digital form, accessible to the board.
  • Minutes of the board and AGM: summarize significant findings, authorized expenditures and planned actions.
  • Postings and labels: ensure that the most recent test dates are visible and up to date.

From a financial perspective, plan for two funding envelopes:

  • Common expenses/condo fees: periodic testing, minor repairs and regular maintenance visits.
  • Contingency fund: major upgrading or long-term replacement of the pump assembly, based on the EUC and the service life anticipated by your professionals.

The board must align its maintenance schedule with insurance renewals, municipal inspections and maintenance projects involving other common portions (for example, tanks, the generator and sprinklers). Close monitoring reduces the risk of damage and supports the continuity of protection systems.

For useful tools, browse our blog: All our articles. And to estimate the support required, see our service packages.

FAQ

Do all condominiums need a fire pump?

No. The need for a pump depends on the design of the fire-extinguishing system, the building’s height and the required flow rates/pressures. Many sprinklered buildings need one, while others do not. Refer to the building plans, the DCV, the Safety Code and a fire protection contractor for confirmation.

Who can perform the annual flow test?

The annual flow test must be performed by a contractor holding the appropriate fire protection licence and equipped to measure flow and pressure in accordance with NFPA 25. Verify the RBQ licence and require a signed report containing the results, anomalies and recommendations.

What is the difference between a jockey pump and a fire pump?

The jockey pump maintains system pressure and prevents repeated starts. The fire pump provides the significant flow and pressure required during an alarm condition. The jockey pump never replaces the fire pump and must not be used for the main flow tests.

This article provides general information and does not constitute legal advice. Consult a lawyer or notary for your situation.

Do you manage a condominium in Quebec? Discover our service packages or contact us to assess your needs.

Managing your condo building with multiRent

  • Condo management services
  • Condo maintenance logbook
  • Condo management pricing

Areas served: South Shore · Montreal · Laval · Longueuil · Brossard · Boucherville · Saint-Constant · Saint-Amable · Saint-Jérôme

Share

Related posts

04/11/2026

Concierge or Outsourced Maintenance in a Co-ownership


Read more
21/10/2026

Mice and Rats in a Co-ownership: Who Pays?


Read more
06/10/2026

Condo Renovation Security Deposits in Quebec


Read more

Comments are closed.

multiRent — Gestion de copropriétés

Services

Administrative management

Financial management

Operations management

Portal

About Us

The multiRent team

Contact us

Notaries

LinkedIn

RGCQCorporate member of the RGCQ

Resources

RGCQ

CORPIQ

Portal
    Manage Consent

    To give you the best possible experience, we use technologies such as cookies to store and/or access information about your device. Consenting to these technologies lets us process data such as browsing behaviour or unique identifiers on this site. Declining or withdrawing your consent may affect certain features.

    Functional Always active
    Technical storage or access is strictly necessary for the legitimate purpose of enabling the use of a specific service explicitly requested by the subscriber or user, or for the sole purpose of carrying out the transmission of a communication over an electronic communications network.
    Preferences
    The technical storage or access is necessary for the legitimate purpose of storing preferences that are not requested by the subscriber or user.
    Statistics
    The technical storage or access that is used exclusively for statistical purposes. Technical storage or access used exclusively for anonymous statistical purposes. Without a subpoena, voluntary compliance on the part of your internet service provider, or additional records from a third party, information stored or retrieved for this purpose alone cannot usually be used to identify you.
    Marketing
    Technical storage or access is required to create user profiles in order to send advertising, or to track the user across a website or several websites for similar marketing purposes.
    • Manage options
    • Manage services
    • Manage {vendor_count} vendors
    • Read more about these purposes
    Manage preferences
    • {title}
    • {title}
    • {title}